ATS Panels Electrical Specifications
In this page, we publish the typical electrical and miscellaneous specifications for a contactor changeover and motorised changeover ATS panels. The specifications cover all electrical, electronic and mechanical aspects. Despite this web page, we can supply custom ATS panels up to 2000kVA: ask for an offer today to bernini@bernini-design.com
15-160kVA ATS Panels Mandatory Installation Requirements
1) The panel must be installed only by qualified personnel.
2) Electrical protection devices must be installed to limit the power and current flowing through the panel, from the mains or generator, to the declared curretn rating of the ATS panel.
3) Neutral and ground connections for the ATS panel, mains and generator are mandatory.
4) The negative battery terminal must be grounded on the engine side. Do not ground the negative battery inside the panel.
5) Do not open the door when mains or generator voltage is present. The panel's interior contains components that present a risk of direct contact (IP00).
6) Consider placing advice about the presence of a standby generator on critical points.
7) To interface the engine for an automatic start, browse the tutorial about the Be242 ATS controller.
15kVA AMF Panel (Contactor-Changeover)
| 15kVA Panel Description | Notes |
| Model-ATS (Serial No.) | 15 kVA - Be242 (Nr. serie A-XXX) |
| Structure / Protection | Steel 1,5mm IP62 |
| External Dimensions | 600 X400 X200 / 15KG |
| Rated Power | 15 kVA @ 35°C |
| Continuous Rated Power | 12 kVA @ 40°C |
| Rated Voltage | 400Vac / 360-440Vac |
| Insulation Voltage | 1000Vac |
| Rated Current AC1 | 28 Amp |
| Continuous Current / Short Circuit | 0-22 A / 50 kA |
| Frequency / Range | 50Hz / 45-55Hz |
| Electrical Protections | Min-Max V-Hz, Max Amp |
| Contactors | 3-Ph+N Lovato BF12T4A |
| Norms / Standards | IEC 61439-1-2-34-5-6-7 IEC 60529 |
| Internal Protections | 2 x Circuit Breakers10A |
| Humidity Class | 5-85% |
| Operating Temperature | -5/+35 °C Nominal (50°C max.) |
| Temperature-Dependent Power Reduction | Reduce the power by 2% for each degree °C above 35 °C. |
| Connections | 12X16 mmq |
| Battery Charger | 12 V / 2 A |
| Standby Power Supply | 10 VA |
25kVA AMF Panel (Contactor-Changeover)
| Description | Notes |
| Model-ATS (Serial No.) | 25 kVA - Be242 (Nr. serie A-XXX) |
| Structure / Protection | Steel 1,5mm IP62 |
| External Dimensions | 600 X400 X210 / 18KG |
| Rated Power @ 30°C | 25 kVA @ 36A @ 400V |
| Continuous Rated Power @ 40°C | 20 kVA @ 30A @ 400V |
| Rated Voltage | 400Vac / 360-440Vac |
| Insulation Voltage | 1000Vac |
| Rated Current AC1 | 45 Amp |
| Continuous Current / Short Circuit | 0-36 A @ 30°C @ 400V /50kA |
| Frequency / Range | 50Hz / 45-55Hz |
| Electrical Protections | Min-Max V-Hz, Max Amp |
| Contactors | 3-Ph+N Lovato BF26T4A |
| Norms / Standards | IEC 61439-1-2-34-5-6-7 IEC 60529 |
| Internal Protections | 2 x Circuit Breakers10A |
| Humidity Class | 5-85% |
| Operating Temperature | -5/+35 °C Nominal (50°C max.) |
| Temperature-Dependent Power Reduction | Reduce the power by 2% for each degree °C above 35 °C. |
| Connections | 12X16 mmq |
| Battery Charger | 12 V / 1 A |
| Standby Power Supply | 10 VA |
40kVA AMF Panel (Contactor-Changeover)
| Description | Notes |
| Model-ATS (Serial No.) | 40 kVA - Be242 (Nr. serie A-XXX) |
| Structure / Protection | Steel 1,5mm IP62 |
| External Dimensions | 700 X500 X200(mm) / 25kg |
| Rated Power (30°C) | 40 kVA @ 30°C @ 58A @ 400V |
| Continuous Rated Power (40°C) | 35 kVA @ 40°C @ 51A @ 400V |
| Rated Voltage | 400Vac / 360 - 440Vac |
| Insulation Voltage | 1000 Vac |
| Rated Current AC1 | 70 A |
| (Short Circuit) | @ 400V /50kA |
| Frequency / Range | 50Hz / 45-55Hz |
| Electrical Protections | Min-Max V-Hz, Max Amp |
| Contactors | 3-Ph+N Lovato BF40T4A |
| Norms / Standards | IEC 61439-1-2-34-5-6-7 IEC 60529 |
| Internal Protections | 2 x Circuit Breakers10A |
| Humidity Class | 5-85% |
| Operating Temperature | -5/+35 °C Nominal (50°C max.) |
| Temperature-Dependent Power Reduction | Reduce the power by 2% for each degree °C above 35 °C. |
| Connections | 12X25 mmq terminal blocks |
| Battery Charger | 12 V / 1 A |
| Standby Power Supply | 15 VA |
60kVA AMF Panel (Contactor-Changeover)
| Description | Notes |
| Model-AMF (Serial No.) | 60 kVA - BeK3 (Nr. serie A-XXX) |
| Structure / Protection | Steel 1,5mm IP62 |
| External Dimensions | 700 X500 X260 / 27kg |
| Maximum Rated Power | 78 kVA @ 35°C |
| Continuous Rated Power | 60 kVA @ 35°C |
| Rated Voltage | 400 Vac / 360-440 Vac |
| Insulation Voltage | 1000 Vac |
| Rated Current AC1 | 115 Amp |
| Continuous Current / Short Circuit | 0-86 Amp @ 400 V /50 kA |
| Frequency / Range | 50 Hz / 45-55 Hz |
| Electrical Protections | Min-Max V-Hz, Max Amp |
| Changeover | 2 X contactor BF80T4A |
| Norms / Standards | IEC 61439-1-2-34-5-6-7 IEC 60529 |
| Internal Protections | 2 x Circuit Breakers10A 4-pole |
| Humidity Class | 5-85% |
| Operating Temperatures | -5/+35 °C Nominal (50°C max.) |
| Temperature-Dependent Power Reduction | Reduce the power by 5% for each degree °C above 35 °C. |
| Connections | 12X35 mmq terminal block |
| Battery Charger | 12 V / 2 A |
| Standby Power Supply | 20 VA |
80kVA ATS Panel (Motorized-Changeover)
Detailed specifications for the 80kVA 125A 3Ph+N with Motorized ATS Control Panel. Built by Bernini Design Srl with a 5-year warranty, IEC compliance, and Canbus (J1939) Modbus remote monitoring via BeK3 AMF controller
Order the panel to: bernini@bernini-design.com
| Description | Notes |
| Manufacturer - Production Date | Bernini Design Srl -........ |
| Model-ATS (Serial No.) | 80 kVA - BEK3 (Nr....) |
| Structure / Protection | Steel 1,5mm IP62 |
| External Dimensions | 70 X50 X26 / 26KG |
| Rated Power (*) / Ac1 Current | 80 kVA @ 35°C / 125 A |
| Continuous Rated Power / Current | 69 kVA @ 35°C / 100A |
| Rated Voltage | 400 V / 360-440 |
| Insulation Voltage | 1000 V |
| Rated Current AC1 | 125 A |
| Continuous Current / Short Circuit | 0-100 A @ 400 V /50 kA |
| Frequency / Range | 50 Hz / 45-55 Hz |
| Electrical Protections | See BeK3 specifications |
| Changeover | 3-Ph+N TELERGON 125A |
| Norms / Standards | IEC 61439-1-2-34-5-6-7 IEC 60529 |
| Internal Protections | 2 x Circuit Breakers 10 A |
| Humidity Class | 5-85 % |
| Operating Temperatures | -5 /+35 °C Nominal (50°C max.) |
| Temperature-Dependent Power Reduction | Reduce power by 5% for each °C above 35. |
| Connections /CT size | 12 X M8 bolt / 150A-5A |
| Battery Charger | 12 V / 2 A |
| Standby Power Supply | 10 VA |
130kVA ATS Panel (Contactor-Changeover)
Order the panel to: bernini@bernini-design.com
Technical datasheet and specifications for the BeK3-based 130kVA 200A 3Ph+N Motorized Automatic Transfer Switch panel. Designed and manufactures in Eu by Bernini Design it features a 5-year warranty and full IEC compliance. It supports GSM, TCP/IP and Modbus remote control monitoring.
| Description | Notes |
| Manufacturer - Production Date | ernini Design Srl -........ |
| Model-ATS (Serial No.) | 130 kVA - BEK3 (Nr....) |
| Structure / Protection | Steel 1,5mm IP62 |
| External Dimensions | 70 X50 X26 / 32 kg |
| Rated Power | 130 kVA @ 35°C |
| Continuous Rated Power | 110 kVA @ 35°C |
| Rated Voltage | 400 V / 360-440 |
| Insulation Voltage | 1000 V |
| Rated Current AC1 | 200 A |
| Continuous Current / Short Circuit | 0-160 A @ 400 V /50 kA |
| Frequency / Range | 50 Hz / 45-55 Hz |
| Electrical Protections | See the BeK3 data sheet |
| MTS | 3-Ph+N TELERGON 200A |
| Norms / Standards | IEC 61439-1-2-34-5-6-7 IEC 60529 |
| Internal Protections | 2 x Circuit Breakers 10 A (4-P) |
| Humidity Class | 5-85 % |
| Operating Temperatures | -5 /+35 °C Nominal (50°C max.) |
| Temperature-Dependent Power Reduction | Reduce power by 5% for each °C above 35. |
| Connections /CTs Size | 12 X M10 bolt / 250A-5A |
| Battery Charger | 12 V / 2 A |
| Standby Power Supply | 10 VA |
100kVA ATS Panel 150A (Contactor-Changeover)
Detailed specifications for the 100kVA 15oA 3Ph+N Motorized ATS Control Panel. Built by Bernini Design Srl with a 5-year warranty, totally IEC compliant. Based on BeK3 controller platform, it offers Canbus (J1939), Modbus and remote control & monitoring options.
Order the panel to: bernini@bernini-design.com
| Description | Notes |
| Manufacturer - Production Date | Bernini Design Srl -........ |
| Model-ATS (Serial No.) | 100 kVA - BEK3 (Nr....) |
| Structure / Protection | Steel 1,5mm IP62 |
| External Dimensions | 70 X50 X26 / 28KG |
| Rated Power/ Current (*) | 100 kVA @ 35°C / 150A |
| Continuous Rated Power / Current | 90 kVA @ 35°C / 130A |
| Rated Voltage | 400 V / 360-440 |
| Insulation Voltage | 1000 V |
| Rated Current AC1 | 150 A |
| Continuous Current / Short Circuit | 0-130 A @ 400 V /50 kA |
| Frequency / Range | 50 Hz / 45-55 Hz |
| Electrical Protections | See BeK3 specifications |
| Changeover | 3-Ph+N TELERGON 125A |
| Norms / Standards | IEC 61439-1-2-34-5-6-7 IEC 60529 |
| Internal Protections | 2 x Circuit Breakers 10 A |
| Humidity Class | 5-85 % |
| Operating Temperatures | -5 /+35 °C Nominal (50°C max.) |
| Temperature-Dependent Power Reduction | Reduce power by 5% for each °C above 35. |
| Connections | 12 X 25 mmq |
| Battery Charger | 12 V / 2 A |
| Standby Power Supply | 10 VA |
160kVA ATS Panel 250A (Contactor-Changeover)
Browse the technical datasheet and specifications for the BeK3-based, J1939-compliant, 160kVA 250A 3Ph+N Motorized Automatic Transfer Switch panel. Designed and manufactured in Eu by Bernini Design, it features a 5-year warranty and IEC full compliance. It supports GSM, TCP/IP and Modbus remote control monitoring.
Order the panel to: bernini@bernini-design.com
| Description | Notes |
| Manufacturer - Production Date | Bernini Design Srl -........ |
| Model-ATS (Serial No.) | 160 kVA - BEK3 (Nr....) |
| Structure / Protection | Steel 1,5mm IP62 |
| External Dimensions | 70 X50 X26 / 36 kg |
| Maximum Rated Power (*) | 160 kVA @ 35°C |
| Continuous Rated Power | 140 kVA @ 35°C |
| Rated Voltage | 400 V / 360-440 |
| Insulation Voltage | 1000 V |
| Rated Current AC1 | 250 A |
| Continuous Current / Short Circuit | 0-205 A @ 400 V /50 kA |
| Frequency / Range | 50 Hz / 45-55 Hz |
| Electrical Protections | Min-Max V-Hz, Max Amp |
| MTS | 3-Ph+N TELERGON 250A |
| Norms / Standards | IEC 61439-1-2-34-5-6-7 IEC 60529 |
| Internal Protections | 2 x Circuit Breakers 10 A |
| Humidity Class | 5-85 % |
| Operating Temperatures | -5 /+35 °C Nominal (50°C max.) |
| Temperature-Dependent Power Reduction | Reduce power by 5% for each °C above 35. |
| Connections | 12 X M10 bolt |
| Battery Charger | 12 V / 6 A (24 V 3A) |
| Standby Power Supply | 20 VA |
(*] The maximum rated power is the switching capacity specified for a resistive load in accordance with IEC AC-1 specifications at 400 V - 50 Hz. The continuous rated power is the maximum power, provided that the top surface of the metal cabinet does not exceed 35°C.
Bernini Design Srl Italy
Industrial Park
46035 Ostiglia Italy
bernini@bernini-design.com
+39 335 70 77148