ATS Panels Electrical Specifications

In this page, we publish the typical electrical and miscellaneous specifications for a contactor changeover and motorised changeover ATS panels. The specifications cover all electrical, electronic and mechanical aspects. Despite this web page, we can supply custom ATS panels up to 2000kVA: ask for an offer today to bernini@bernini-design.com

15kVA (Contactors-Changeover)

25kVA (Contactor-Changeover)

40kVA (Contactors-Changeover)

60kVA (Contactors-Changeover)

80kVA (Motorized-Changeover)

100kVA (Motorized-Changeover)

130kVA (Motorized-Changeover)

160kVA (Motorized-Changeover)


15-160kVA ATS Panels Mandatory Installation Requirements

1) The panel must be installed only by qualified personnel.

2) Electrical protection devices must be installed to limit the power and current flowing through the panel, from the mains or generator, to the declared curretn rating of the ATS panel.

3) Neutral and ground connections for the ATS panel, mains and generator are mandatory.

4) The negative battery terminal must be grounded on the engine side. Do not ground the negative battery inside the panel.

5) Do not open the door when mains or generator voltage is present. The panel's interior contains components that present a risk of direct contact (IP00).

6) Consider placing advice about the presence of a standby generator on critical points.

7) To interface the engine for an automatic start, browse the tutorial about the Be242 ATS controller.


15kVA

15kVA AMF Panel (Contactor-Changeover)

PURCHASE THIS PANEL ONLINE

15kVA Panel Description Notes
Model-ATS (Serial No.) 15 kVA - Be242 (Nr. serie A-XXX)
Structure / Protection Steel 1,5mm IP62
External Dimensions 600 X400 X200 / 15KG
Rated Power 15 kVA @ 35°C
Continuous Rated Power 12 kVA @ 40°C
Rated Voltage 400Vac / 360-440Vac
Insulation Voltage 1000Vac
Rated Current AC1 28 Amp
Continuous Current / Short Circuit 0-22 A / 50 kA
Frequency / Range 50Hz / 45-55Hz
Electrical Protections Min-Max V-Hz, Max Amp
Contactors 3-Ph+N Lovato BF12T4A
Norms / Standards IEC 61439-1-2-34-5-6-7 IEC 60529
Internal Protections 2 x Circuit Breakers10A
Humidity Class 5-85%
Operating Temperature -5/+35 °C Nominal (50°C max.)
Temperature-Dependent Power Reduction Reduce the power by 2% for each degree °C above 35 °C.
Connections 12X16 mmq
Battery Charger 12 V / 2 A
Standby Power Supply 10 VA

25kVA

25kVA AMF Panel (Contactor-Changeover)

PURCHASE THIS PANEL ONLINE

Description Notes
Model-ATS (Serial No.) 25 kVA - Be242 (Nr. serie A-XXX)
Structure / Protection Steel 1,5mm IP62
External Dimensions 600 X400 X210 / 18KG
Rated Power @ 30°C 25 kVA  @ 36A @ 400V
Continuous Rated Power @ 40°C 20 kVA   @ 30A @ 400V
Rated Voltage 400Vac / 360-440Vac
Insulation Voltage 1000Vac
Rated Current AC1 45 Amp
Continuous Current / Short Circuit 0-36 A @ 30°C @ 400V /50kA
Frequency / Range 50Hz / 45-55Hz
Electrical Protections Min-Max V-Hz, Max Amp
Contactors 3-Ph+N Lovato BF26T4A
Norms / Standards IEC 61439-1-2-34-5-6-7 IEC 60529
Internal Protections 2 x Circuit Breakers10A
Humidity Class 5-85%
Operating Temperature -5/+35 °C Nominal (50°C max.)
Temperature-Dependent Power Reduction Reduce the power by 2% for each degree °C above 35 °C.
Connections 12X16 mmq
Battery Charger 12 V / 1 A
Standby Power Supply 10 VA

40kVA

40kVA AMF Panel (Contactor-Changeover)

PURCHASE THIS PANEL ONLINE

Description Notes
Model-ATS (Serial No.) 40 kVA - Be242 (Nr. serie A-XXX)
Structure / Protection Steel 1,5mm IP62
External Dimensions 700 X500 X200(mm) / 25kg
Rated Power (30°C) 40 kVA @ 30°C @ 58A @ 400V
Continuous Rated Power (40°C) 35 kVA @ 40°C @ 51A @ 400V
Rated Voltage 400Vac / 360 - 440Vac
Insulation Voltage 1000 Vac
Rated Current AC1 70 A
(Short Circuit)  @ 400V /50kA
Frequency / Range 50Hz / 45-55Hz
Electrical Protections Min-Max V-Hz, Max Amp
Contactors 3-Ph+N Lovato BF40T4A
Norms / Standards IEC 61439-1-2-34-5-6-7 IEC 60529
Internal Protections 2 x Circuit Breakers10A
Humidity Class 5-85%
Operating Temperature -5/+35 °C Nominal (50°C max.)
Temperature-Dependent Power Reduction Reduce the power by 2% for each degree °C above 35 °C.
Connections 12X25 mmq terminal blocks
Battery Charger 12 V / 1 A
Standby Power Supply 15 VA

60kVA

60kVA AMF Panel (Contactor-Changeover)

PURCHASE THIS PANEL ONLINE

Description Notes
Model-AMF (Serial No.) 60 kVA - BeK3 (Nr. serie A-XXX)
Structure / Protection Steel 1,5mm IP62
External Dimensions 700 X500 X260 / 27kg
Maximum Rated Power 78 kVA @ 35°C
Continuous Rated Power 60 kVA @ 35°C
Rated Voltage 400 Vac / 360-440 Vac
Insulation Voltage 1000 Vac
Rated Current AC1 115 Amp
Continuous Current / Short Circuit 0-86 Amp @ 400 V /50 kA
Frequency / Range 50 Hz / 45-55 Hz
Electrical Protections Min-Max V-Hz, Max Amp
Changeover 2 X contactor BF80T4A
Norms / Standards IEC 61439-1-2-34-5-6-7 IEC 60529
Internal Protections 2 x Circuit Breakers10A 4-pole
Humidity Class 5-85%
Operating Temperatures -5/+35 °C Nominal (50°C max.)
Temperature-Dependent Power Reduction Reduce the power by 5% for each degree °C above 35 °C.
Connections 12X35 mmq terminal block
Battery Charger 12 V / 2 A
Standby Power Supply 20 VA

80kVA

80kVA ATS Panel  (Motorized-Changeover)

Detailed specifications for the 80kVA 125A 3Ph+N with Motorized ATS Control Panel. Built by Bernini Design Srl with a 5-year warranty, IEC compliance, and Canbus (J1939) Modbus remote monitoring via BeK3 AMF controller

Order the panel to: bernini@bernini-design.com

Description Notes
Manufacturer - Production Date Bernini Design Srl -........
Model-ATS (Serial No.) 80 kVA - BEK3 (Nr....)
Structure / Protection Steel 1,5mm IP62
External Dimensions 70 X50 X26 / 26KG
Rated Power (*) / Ac1 Current 80 kVA @ 35°C / 125 A
Continuous Rated Power / Current 69 kVA @ 35°C / 100A
Rated Voltage 400 V / 360-440 
Insulation Voltage 1000 V
Rated Current AC1 125 A
Continuous Current / Short Circuit 0-100 A @ 400  V /50 kA
Frequency / Range 50 Hz / 45-55 Hz
Electrical Protections See BeK3 specifications
Changeover 3-Ph+N TELERGON 125A
Norms / Standards IEC 61439-1-2-34-5-6-7 IEC 60529
Internal Protections 2 x Circuit Breakers 10 A
Humidity Class 5-85 %
Operating Temperatures -5 /+35 °C Nominal (50°C max.)
Temperature-Dependent Power Reduction Reduce power by 5% for each °C above 35.
Connections /CT size 12 X M8 bolt / 150A-5A
Battery Charger 12 V / 2 A
Standby Power Supply 10 VA

 


130kVA

130kVA ATS Panel (Contactor-Changeover)

Order the panel to: bernini@bernini-design.com

Technical datasheet and specifications for the BeK3-based 130kVA 200A 3Ph+N Motorized Automatic Transfer Switch panel. Designed and manufactures in Eu by Bernini Design it features a 5-year warranty and full IEC compliance. It supports GSM, TCP/IP and Modbus remote control monitoring.

Description Notes
Manufacturer - Production Date ernini Design Srl -........
Model-ATS (Serial No.) 130 kVA - BEK3 (Nr....)
Structure / Protection Steel 1,5mm IP62
External Dimensions 70 X50 X26 / 32 kg
Rated Power 130 kVA @ 35°C
Continuous Rated Power 110 kVA @ 35°C
Rated Voltage 400 V / 360-440 
Insulation Voltage 1000 V
Rated Current AC1 200 A
Continuous Current / Short Circuit 0-160 A @ 400  V /50 kA
Frequency / Range 50 Hz / 45-55 Hz
Electrical Protections See the BeK3 data sheet
MTS 3-Ph+N TELERGON 200A
Norms / Standards IEC 61439-1-2-34-5-6-7 IEC 60529
Internal Protections 2 x Circuit Breakers 10 A (4-P)
Humidity Class 5-85 %
Operating Temperatures -5 /+35 °C Nominal (50°C max.)
Temperature-Dependent Power Reduction Reduce power by 5% for each °C above 35.
Connections /CTs Size 12 X M10 bolt / 250A-5A
Battery Charger 12 V / 2 A
Standby Power Supply 10 VA

 


100kVA

100kVA ATS Panel 150A (Contactor-Changeover)

 Detailed specifications for the 100kVA 15oA 3Ph+N Motorized ATS Control Panel. Built by Bernini Design Srl with a 5-year warranty, totally IEC compliant. Based on BeK3 controller platform, it offers Canbus (J1939), Modbus and remote control & monitoring options.

Order the panel to: bernini@bernini-design.com

Description Notes
Manufacturer - Production Date Bernini Design Srl -........
Model-ATS (Serial No.) 100 kVA - BEK3 (Nr....)
Structure / Protection Steel 1,5mm IP62
External Dimensions 70 X50 X26 / 28KG
Rated Power/ Current (*) 100 kVA @ 35°C / 150A
Continuous Rated Power / Current 90 kVA @ 35°C / 130A
Rated Voltage 400 V / 360-440 
Insulation Voltage 1000 V
Rated Current AC1 150 A
Continuous Current / Short Circuit 0-130 A @ 400  V /50 kA
Frequency / Range 50 Hz / 45-55 Hz
Electrical Protections See BeK3 specifications
Changeover 3-Ph+N TELERGON 125A
Norms / Standards IEC 61439-1-2-34-5-6-7 IEC 60529
Internal Protections 2 x Circuit Breakers 10 A
Humidity Class 5-85 %
Operating Temperatures -5 /+35 °C Nominal (50°C max.)
Temperature-Dependent Power Reduction Reduce power by 5% for each °C above 35.
Connections 12 X 25 mmq
Battery Charger 12 V / 2 A
Standby Power Supply 10 VA

 


160kVA

160kVA ATS Panel 250A (Contactor-Changeover)

Browse the technical datasheet and specifications for the BeK3-based, J1939-compliant, 160kVA 250A 3Ph+N Motorized Automatic Transfer Switch panel. Designed and manufactured in Eu by Bernini Design, it features a 5-year warranty and IEC full compliance. It supports GSM, TCP/IP and Modbus remote control monitoring.

Order the panel to: bernini@bernini-design.com

Description Notes
Manufacturer - Production Date Bernini Design Srl -........
Model-ATS (Serial No.) 160 kVA - BEK3 (Nr....)
Structure / Protection Steel 1,5mm IP62
External Dimensions 70 X50 X26 / 36 kg
Maximum Rated Power (*) 160 kVA @ 35°C
Continuous Rated Power 140 kVA @ 35°C
Rated Voltage 400 V / 360-440 
Insulation Voltage 1000 V
Rated Current AC1 250 A
Continuous Current / Short Circuit 0-205 A @ 400  V /50 kA
Frequency / Range 50 Hz / 45-55 Hz
Electrical Protections Min-Max V-Hz, Max Amp
MTS 3-Ph+N TELERGON 250A
Norms / Standards IEC 61439-1-2-34-5-6-7 IEC 60529
Internal Protections 2 x Circuit Breakers 10 A
Humidity Class 5-85 %
Operating Temperatures -5 /+35 °C Nominal (50°C max.)
Temperature-Dependent Power Reduction Reduce power by 5% for each °C above 35.
Connections 12 X M10 bolt
Battery Charger 12 V / 6 A (24 V 3A)
Standby Power Supply 20 VA

(*] The maximum rated power is the switching capacity specified for a resistive load in accordance with IEC AC-1 specifications at 400 V - 50 Hz. The continuous rated power is the maximum power, provided that the top surface of the metal cabinet does not exceed 35°C.


Bernini Design Srl Italy

Home

Industrial Park
46035 Ostiglia Italy
bernini@bernini-design.com
+39 335 70 77148

 

Scroll to Top